Multifunctional bay controller MIR KPR-01M

Multifunctional bay controller MIR KPR-01M is used as part of industrial AMI

Multifunctional bay controller MIR KPR-01M

Add to cart

Цена по запросу

Прайс-лист

Purpose

  Multifunctional bay controller MIR KPR-01M is used as part of industrial AMI
  The device has optional functions of measurement transducer, faults recorder, energy quality monitor.

  Functions

– data collection from protection relays, field devices and intellectual devices;
– prompt blocking;
– support of IEC 61850-8 (MMS/GOOSE); IEC 870-5-101/104, ModBus RTU/TCP protocols and proprietary manufacturers protocols;
– ability of expansion with I/O modules and display units.
– instrumentation parameters monitoring and recording;
– electric energy metering with load profiles storing;
– oscillograms recording with prefault history recording;
– recording discrete signals on the state of the equipment;
– issuing control commands.



Interfaces:

– one CAN interface;
– one RS232;
– up to 4 RS-485 interfaces;
– 2 Ethernet 100BASE-TX interfaces with ring topology support and with hardware Bypass function;
– interface external indicator (LCD or LED) (24V).

Specifications:

– rated phase voltage 57.7-230 V;
– rated (maximum) current 1-5 (10) A or 5 (150) A;
– 8 discrete channels with a rated voltage of 24V;
– 2 discrete outputs;
– powered by 24V or 230V.

Discrete input channels characteristics

Parameter name

Value

Number of channels 8 for voltage of 24 V or 230 V
The minimum duration of the signal at the discrete channel input 1 ms
Contact debouncing time 1 ms – 60 s, discreetness 1 ms
Insulation strength 4 kV
Channel interrogate rated current 5 mA
The external circuit resistance, at which the "closed" state is fixed 150 Ohm and less
The external circuit resistance, at which the "open" state is fixed 50 kOhm and more

Discrete output channels characteristics

Parameter name

Value

Number of channels 2
Channels switching capacity when switching AC   5 A, 230 V, load class AC1
1.3 А, 230 V, load class AC15
Channels switching capacity when switching DC   0.3 A, 230 V, load class DC1, DC13
5 A, 24 V, load class DC1, DC13
Switching relay lifetime not less than 30,000 cycles
Insulation strength between channels 2 kV
Group of discrete output channels insulation strength 4 kV
Control pulse duration 10 ms – 60 s, discreteness 10 ms, or continuously

Power supply characteristics

Parameter name

Value

Power supply rated voltage 224VDC
230 V AC
Power consumption  not more than 16 VA at rated voltage of 230 V   
not more than 6 W at rated voltage of 12 V  

background